Heidelberg Materials - Matera
Emissioni Forno
Analisi Valori Medi
| Polveri | ||
| Ossidi di zolfo [SO2] | ||
| Ossidi di azoto [NOx come NO2] | ||
| Ossido di carbonio [CO] | ||
| Acido cloridrico [HCl] | ||
| Carbonio Organico totale [TOC] | ||
| Ammoniaca [NH3] |
[Mese Precedente] [Mese Successivo] [Anno 2026] [Principale]
| |
Polveri @ 10%O2 - convalidato mg/Nm³ |
SO2 @ 10%O2 - convalidato mg/Nm³ |
NOx @ 10%O2 - convalidato mg/Nm³ |
CO @ 10%O2 - convalidato mg/Nm³ |
HCl @ 10%O2 - convalidato mg/Nm³ |
TOC @ 10%O2 - convalidato mg/Nm³ |
NH3 @ 10%O2 - convalidato mg/Nm³ |
| 01/03/2026 | 2.9 * | 3.3 * | 383.2 * | 351.9 * | 2.3 * | 14.3 * | 1.9 * |
| 02/03/2026 | 3.8 | 3.3 | 396.1 | 439.8 | 0.6 | 14.9 | 3.1 |
| 03/03/2026 | 3.8 | 3.3 | 373.5 | 492.5 | 0.5 | 16.5 | 2.6 |
| 04/03/2026 | 2.2 | 3.9 | 400.7 | 285.7 | 0.5 | 15.0 | 4.7 |
| 05/03/2026 | 2.2 | 3.3 | 388.4 | 401.7 | 0.5 | 17.0 | 2.6 |
| 06/03/2026 | 3.4 | 3.3 | 387.3 | 424.0 | 0.5 | 17.0 | 2.9 |
| 07/03/2026 | 4.7 | 3.5 | 413.0 | 446.5 | 0.5 | 18.8 | 4.9 |
| 08/03/2026 | 5.4 | 10.3 | 414.0 | 418.4 | 0.6 | 17.8 | 11.7 |
| 09/03/2026 | 4.6 | 3.3 | 413.4 | 380.8 | 0.5 | 14.7 | 1.9 |
| 10/03/2026 | 5.2 | 3.7 | 398.2 | 463.6 | 0.5 | 17.3 | 3.3 |
| 11/03/2026 | 5.5 | 3.3 | 395.4 | 477.1 | 0.5 | 17.0 | 1.9 |
| 12/03/2026 | 5.8 | 3.3 | 396.7 | 478.0 | 0.5 | 14.4 | 1.9 |
| 13/03/2026 | 6.1 | 3.3 | 388.4 | 475.6 | 0.5 | 15.7 | 3.9 |
| 14/03/2026 | 7.5 | 3.3 | 359.4 | 477.3 | 0.5 | 18.3 | 4.5 |
| 15/03/2026 | 7.4 | 3.3 | 410.7 | 532.1 | 0.5 | 15.9 | 7.4 |
| 16/03/2026 | 8.0 | 3.3 | 401.7 | 466.8 | 0.5 | 14.6 | 5.4 |
| 17/03/2026 | 8.1 | 3.3 | 372.9 | 381.4 | 0.5 | 14.5 | 3.0 |
| 18/03/2026 | N.A. | N.A. | N.A. | N.A. | N.A. | N.A. | N.A. |
| 19/03/2026 | 1.4 * | 3.3 * | 395.0 * | 469.6 * | 1.5 * | 14.9 * | 1.9 * |
| 20/03/2026 | 1.4 | 3.3 | 405.8 | 497.0 | 0.5 | 14.9 | 2.4 |
| 21/03/2026 | 1.5 | 3.3 | 400.7 | 358.6 | 1.2 | 15.1 | 2.7 |
| 22/03/2026 | 1.5 | 3.3 | 407.5 | 491.1 | 0.5 | 13.9 | 2.4 |
| 23/03/2026 | 1.8 | 3.3 | 413.9 | 425.3 | 0.5 | 13.0 | 6.5 |
| 24/03/2026 | 2.0 | 3.3 | 416.0 | 429.4 | 0.5 | 12.4 | 3.0 |
| 25/03/2026 | 2.1 | 3.3 | 418.4 | 452.6 | 0.5 | 12.4 | 6.1 |
| 26/03/2026 | 2.5 | 3.3 | 405.9 | 417.8 | 0.5 | 13.0 | 3.6 |
| 27/03/2026 | 2.6 | 3.3 | 406.8 | 491.3 | 0.5 | 11.6 | 1.9 |
| 28/03/2026 | 2.6 | 3.3 | 400.6 | 481.5 | 0.5 | 8.8 | 3.0 |
| 29/03/2026 | 3.0 | 3.3 | 400.0 | 436.2 | 0.5 | 10.5 | 3.2 |
| 30/03/2026 | 3.3 | 3.3 | 381.1 | 448.0 | 0.5 | 11.9 | 3.2 |
| 31/03/2026 | 3.5 | 3.3 | 399.7 | 414.8 | 0.5 | 12.1 | 5.2 |
| Soglia | 10.0 | 50.0 | 450.0 | 600.0 | 10.0 | 30.0 | 30.0 |
| Nr Sup. | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
| Max | 8.1 | 10.3 | 418.4 | 532.1 | 1.2 | 18.8 | 11.7 |
| Min | 1.4 | 3.3 | 359.4 | 285.7 | 0.5 | 8.8 | 1.9 |
| |
Polveri @ 10%O2 - convalidato mg/Nm³ |
SO2 @ 10%O2 - convalidato mg/Nm³ |
NOx @ 10%O2 - convalidato mg/Nm³ |
CO @ 10%O2 - convalidato mg/Nm³ |
HCl @ 10%O2 - convalidato mg/Nm³ |
TOC @ 10%O2 - convalidato mg/Nm³ |
NH3 @ 10%O2 - convalidato mg/Nm³ |
| Mese | 4.0 | 3.5 | 398.7 | 442.9 | 0.5 | 14.6 | 3.7 |
| SemiOre valide | 1245 | 1245 | 1245 | 1245 | 1245 | 1245 | 1245 |
| SemiOre N.F. | 1322 | 1322 | 1322 | 1322 | 1322 | 1322 | 1322 |
[Mese Precedente] [Mese Successivo] [Anno 2026] [Principale]
| Non Valido - Le misurazioni non sono significative in quanto durante il periodo le apparecchiature od il sistema di misurazione ha dichiarato malfunzionamenti, quindi le misurazioni effettuate non sono attendibili. - Lo stato dell'impianto controllato è relativo a momenti di esercizio transitorio (avviamento o fermata). | |
| Non Applicabile Durante la giornata l'impianto controllato ha superato lo stato di minimo tecnico per una durata inferiore alla mimima richiesta, quindi il valore medio calcolato non è significativo (ex DM 21/12/1995). L'impianto controllato, per quanto concerna la media aggregata, è da considerare fermo | |
| Non Disponibile Le informazioni per la grandezza non sono disponibili a causa di problemi tecnici del sistema di misurazione o memorizzazione. | |
| Fuori Scansione Le informazioni non sono state effettuate a causa di guasto o manutenzione delle apparecchiature di misurazione. | |
| Superamento soglia normativa Il valore medio misurato è superiore al valore massimo ammissibile. |
PF Sistemi s.r.l. Milano