Italcementi - Matera 
Emissioni Forno 
Analisi Valori Medi 

LIMITI DI EMISSIONE (dal 01/01/2018)

Polveri
10
[mg/Nm3]
Ossidi di zolfo [SO2]
50
[mg/Nm3]
Ossidi di azoto [NOx come NO2]
450
[mg/Nm3]
Ossido di carbonio [CO]
600
[mg/Nm3]
Acido cloridrico [HCl]
10
[mg/Nm3]
Carbonio Organico totale [TOC]
30
[mg/Nm3 come C]
Ammoniaca [NH3]
30
[mg/Nm3]

  [Mese Precedente]    [Mese Successivo]    [Anno 2021]    [Principale]

 

Mensile lineare 03/2021
 
 
Polveri @ 10%O2 
- convalidato 
 
mg/Nm³
 
SO2 @ 10%O2 - 
convalidato 
 
mg/Nm³
 
NOx @ 10%O2 - 
convalidato 
 
mg/Nm³
 
CO @ 10%O2 - convalidato 
 
 
mg/Nm³
 
HCl @ 10%O2 - 
convalidato 
 
mg/Nm³
 
TOC @ 10%O2 - 
convalidato 
 
mg/Nm³
 
NH3 @ 10%O2 - 
convalidato 
 
mg/Nm³
01/03/2021 0.4 5.5 368.1 221.8 0.6 9.7 5.7
02/03/2021 0.4 3.6 356.9 282.7 0.6 9.1 4.2
03/03/2021 0.4 4.7 321.6 284.2 0.6 8.0 6.1
04/03/2021 0.4 4.5 341.8 232.8 0.6 7.7 4.9
05/03/2021 0.4 4.0 321.5 294.4 0.6 8.0 4.5
06/03/2021    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.
07/03/2021    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.
08/03/2021    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.
09/03/2021    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.
10/03/2021    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.
11/03/2021    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.
12/03/2021    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.
13/03/2021    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.
14/03/2021    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.
15/03/2021    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.
16/03/2021    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.
17/03/2021    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.
18/03/2021    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.
19/03/2021    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.
20/03/2021    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.
21/03/2021    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.
22/03/2021    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.
23/03/2021    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.
24/03/2021    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.
25/03/2021    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.
26/03/2021    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.
27/03/2021    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.
28/03/2021    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.
29/03/2021    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.
30/03/2021    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.    N.A.
31/03/2021 0.0 * 0.0 * 0.0 * 0.0 * 0.0 * 0.0 * 0.0 *
  
Soglia 10.0 50.0 450.0 600.0 10.0 30.0 30.0
Nr Sup. 0 0 0 0 0 0 0
Max 0.4 5.5 368.1 294.4 0.6 9.7 6.1
Min 0.4 3.6 321.5 221.8 0.6 7.7 4.2
  
 
  
 
Polveri @ 10%O2 
- convalidato 
 
mg/Nm³
 
SO2 @ 10%O2 - 
convalidato 
 
mg/Nm³
 
NOx @ 10%O2 - 
convalidato 
 
mg/Nm³
 
CO @ 10%O2 - convalidato 
 
 
mg/Nm³
 
HCl @ 10%O2 - 
convalidato 
 
mg/Nm³
 
TOC @ 10%O2 - 
convalidato 
 
mg/Nm³
 
NH3 @ 10%O2 - 
convalidato 
 
mg/Nm³
Mese 0.4 4.4 341.0 262.5 0.6 8.5 5.0
SemiOre valide 238 238 238 238 238 238 238
SemiOre N.F. 265 265 265 265 265 265 265
  

  [Mese Precedente]    [Mese Successivo]    [Anno 2021]    [Principale]


Legenda MESE

*
Non Valido
- Le misurazioni non sono significative in quanto durante il periodo le apparecchiature od il sistema di misurazione ha dichiarato malfunzionamenti, quindi le misurazioni effettuate non sono attendibili.
- Lo stato dell'impianto controllato è relativo a momenti di esercizio transitorio (avviamento o fermata).
N.A.
Non Applicabile
Durante la giornata l'impianto controllato ha superato lo stato di minimo tecnico per una durata inferiore alla mimima richiesta, quindi il valore medio calcolato non è significativo (ex D.Lgs. 152/06). L'impianto controllato, per quanto concerna la media aggregata, è da considerare fermo
N.D.
Non Disponibile
Le informazioni per la grandezza non sono disponibili a causa di problemi tecnici del sistema di misurazione o memorizzazione.
F.S.
Fuori Scansione
Le informazioni non sono state effettuate a causa di guasto o manutenzione delle apparecchiature di misurazione.
>
Superamento soglia normativa
Il valore medio misurato è superiore al valore massimo ammissibile.

 

 

Italcementi - Matera - 752-0100-00 